Bulb Wells Description Bulb Wells are used in conjunction with Remote Bulb Temperature Controls where bulb insertion into a vessel or container to sense temperature is required. These wells are used with TE-6000 and TE-6300 Series Sensors. A variety of shapes, sizes, and materials are available for a wide range of applications. Refer to the appropriate temperature control for the exact bulb well required. Figure 27: WEL Series Bulb Well 1 Figure 28: WEL Series Bulb Well 2 Figure 29: WEL Series Bulb Well 3 Accessories The Code No. FTG13A-600R Packing Nut Assembly is used in applications where the temperature does not fall below -35°F (-37°C). The maximum liquid pressure limit is 150 psig (1,034 kPa). Use with Style 1, 3/8 in. diameter bulb for direct immersion application. A19s require models with support tube; A70s and A72s do not need support tubes. Figure 30: FTG13A-600R 108