RLD-H10G Refrigerant Leak Detector technical specifications Table 229: RLD-H10G Refrigerant Leak Detector technical specifications Specification Description Product RLD-H10G Refrigerant Leak Detector Power Requirements 120 VAC at 60 Hz Sensing Element Type Positive Ion Emission Heated Diode Approximate Sensitivity Switch Position Alarm Sensitivity (moving probe) Small >0.05 oz per year CFC or HCFC; >0.5 oz per year HFC Medium >0.5 oz per year CFC or HCFC; >1.0 oz per year HFC Large >3.0 oz per year CFC or HCFC; >5.0 oz per year HFC Leak Alarm Audible alarm, visible neon lamp Response Time Approximately 1 second Warm-up Time Approximately 2 minutes Accuracy Meets SAE J1627 test requirements Probe Length Approximately 4.5 ft (1.4 m) Ambient Operating Conditions 32 to 113° F (0 to 45° C); 5 to 90% RH, non-condensing Ambient Storage Conditions 14 to 140° F (-10 to 60° C); 5 to 90% RH, non-condensing Case Vinyl Dimensions (H x W x D) 2.8 x 8.8 x 5.0 in. (71 x 224 x 127 mm) Shipping Weight 3.2 lbs (1.4 kg) 204 Refrigeration Products Catalog