Wolseley

PENN Controls Products Catalog

Issue link: https://boomart.uberflip.com/i/1442607

Contents of this Issue

Navigation

Page 274 of 367

V246 Series Two-Way Pressure-Actuated Water-Regulating Valves for High-Pressure Refrigerants technical specifications Table 295: V246 Series Two-Way Pressure-Actuated Water-Regulating Valves for High-Pressure Refrigerants Specification Description Factory-set opening point 200 psig (13.8 bar) Maximum working pressure 630 psig (43.4 bar) Opening point adjustment range 200 psi to 400 psi (13.8 bar to 27.6 bar) Media 150 psig (10.3 bar) maximum, -4°F to 170°F (-20°C to 77°C) glycol/water or liquids with low freezing points that are compatible with valve materials Compliance United States: cULus Listed; UL 207 File SFJQ.SA45221 Canada: cULus Listed; UL 207 File SFJQ7.SA45221 Applies to: • V246GA1-001C • V246GB1-001C • V246HA1-001C • V246HB1-001C Note: • The valve body and internal parts are not compatible with ammonia (R717). • The design pressure marked on these components shall not be less than the installed system working pressure or less than the values outlined in ASHRAE 15 for the charged refrigerant. After charging, mark the installed equipment with the refrigerant type and oil used. 275 Refrigeration Products Catalog